Monday, 22 February 2016
Thursday, 18 February 2016
Wednesday, 17 February 2016
Tuesday, 16 February 2016
Power Flow Analysis: Transmission and Distribution Systems:
Power
flow or load flow is one of the important power system analyses.
Problem. This problem is determining the unspecified (dependent)
parameters of the power network by some specified (independent)
parameters.
It
is known that the power system consists of generators, loads,
transformers, transmission lines and other protective devices. In power
flow every bus (node) is having four parameters.
1. Real Power P
2. Reactive power Q
3. Voltage magnitude [V]
4. Voltage magnitude φ
Depending
on the type of the bus two out the four variables are specified and the
remaining two has to be determined. The specified two variables and
unspecified two variables of each bus are related by the kirchoff’s
network laws.
The network elements are modeled according to their steady state characteristics.
1. Generator –voltage source with series impedance
2. Loads: constant power or constant admittance (impedance)
3. Transmission line: pi model
4. Transformers are to be incorporated in the transmission line model.
The specified and unspecified parameters
| ||
Type of the bus
|
Specified variables
|
Unspecified variables
|
Slack
|
[V],φ
|
P,Q
|
Generator
|
[V],P
|
Q, φ
|
Load(Constant power)
|
P,Q
|
[V], φ
|
When
the power is transmitted from the generators to the loads through the
transmission line the loss occurring in the transmission line is
unavoidable. It is call the transmission loss and it not known in
advance so there must be a provision that a generator should include the
transmission loss in its generation.
This
is the reason why the slack bus concept is included in the power flow
analysis. The generator having largest capacity is chosen as the slack
bus. Depending on the selection of the slack bus generator the power
flow solution will vary.
Procedure to solve transmission system power flow
The
following steps are to be followed to carry out power flow analysis.
Here it is assumed that the three phase network is a balanced one.
- Collect the specified data of generators, loads, transmission lines, and transformers. You can follow some matrix format like matpower.
- Convert the network as per unit equivalent.
- Formulate the equations as per kirchooff’s law.
These
equations can be written in either polar form or rectangular form. In
polar form no of equation are to be solved in 2(n-1)-m, wherein the
rectangular form the no of equations are 2(n-1).
- The system of non linear (polar trigonometric, rectangular quadratic) equations are to be solved by numerical methods only because so far no analytical solution is derived to sole this problem.
- Newton Raphson method, Decupled and gauss seidal are methods used to solve this problem. Among this N-R and Decoupled are preferred for their quadratic convergence.
Distribution Power flow.
The
distribution systems are characterized by their nature of high R/X
ration and radial nature (no loop).The admittance matrix is sparse and
the Newton Raphson method may fail to converge for some networks. So the
modeling of the problem as well as the solution methodology is
different.
The
power flow equations for a radial distribution system are derived as
the relationship between the specified complex bus powers and the bus
voltages. If the network has n (total number) buses and ‘m’ generator buses the power flow equations are written as follows
k(i) is the set of nodes connected to node i, and Pi /Qi
denote the real/reactive power at node i. The complex non linear
equations (B2) are to be solved to determine the bus voltages. So many
methods ranging form sweep methods to conic programming methods
available in the literature
to solve this problem..
Monday, 15 February 2016
SGP BITS
1. Oil immersed type reactors are used for voltages __________.
2. A circuit breaker is essentially _________.
3. The arcing contacts for a circuit are made up of ______.
4. The fault clearing time of a circuit breaker is usually of ________.
5. For modern circuit breakers, the time of closing the cycle is _______.
6. The pressure of air used in air blast circuit breakers is around _____.
7. The rating of circuit breaker is usually determined on the basis of ____.
8. Busbars are usually made of _______.
9. A fuse is normally a ___________.
10. Buchholz relay is a ___________.
11. Mho relays have an R-X plane characteristic depicted by __________.
12. Under voltage relays are mostly used for _______.
13. Differential relays are used for protection of equipment against _________.
14. Earth fault relays are _____________.
15. Reactance relay are employed for phase fault in ____________.
16. Location of lightning arrestor is near a ___________.
17. Grounding is done generally at _______.
18. A relay used on short transmission line is ___________.
19. In tap changing transformers, the tappings are provided on _______.
20. Which of the following is a static excitor?
21. Which of the following equipment is not installed in a substation?
22. The recovery voltage will be maximum for power factor of ____.
23. Arc chutes are used in _______________.
24. Breaking capacity of circuit breakers is usually expressed in ___________.
25. Earth wire is made of ______.
25. Earth wire is made of ______.
26. A Buchholz relay protect a transformer from__________
27. In Mertz –Price protection, the CT’s secondary of delta – star power transformer will be in______________
28. For transformer protection, a differential relay is biased to avoid mal operation due to_____________
29.The percentage bias for a generator protection lies between____
30.For the protection of transformers, harmonic restraint is used to guard against_________________
31.The bus-bar zone faults are generally__________
32.A line trap in a long transmission line is used to _________
33.First zone distance relay protects a transmission line section up to full length.___________
34.The over voltage surges in the power systems may be caused by___________
35.Location of lightning arrestors is near a___________
36.The reflection coefficient of a short circuited line is ___________
37.In railway applications Circuit Breakers is used__________
38.Arc is initiated due to___________
39.Current zero interruption method used in________
40.Minimum oil circuit breakers use oil for_____________
41.Making capacity of a circuit breaker is equal to_____________
42.Arc in a circuit behaves as a____________
43.Differential relays are used for protection of___________
44.The relay used on short transmission lines____________
45.Both voltage and current signals are required for____________
46.Differential relays used for the protection of equipment against________
47.Auto reclosure improves what type of stability.___________
48.what is the power factor of an arc?_________
49.Peterson coil has a reactance called?__________
50.what is the rating of SF6?___________KEY
1. above 33kv
2. arc extinguisher
3. copper tungsten alloy
4. few cycles of supply voltage
5. 0.003 sec
6. 20kg/cm2
7. symmetrical faults
8.copper
9current limiting devices
10. gas actuated relay
11.a circle passing through origin
12 motor protection
13. internal faults
14. directional relay
15. short lines
16 transformer
17 supply end
18 reactance relay
19 secondary winding
20 rectifier
21. exiters
22 unity
23 air blast CB
24 MVA
25 galvanised standered steel
26 internal faults
27 star – delta
28 inrush currents
29 5-10
30 swithing over voltages
31 single line to ground
32 confined the carrier signals in the line
33 80%
34 switching
35 transformer
36 -1
37 air blast
38 current between contacts
39 AC circuit breakers
40 arc quenching
41 2.55 times of symmetrical breaking capacity
42 resistance increases voltage increases
43 transformers
44 reactance relay
45 directional relay
46 internal faults
47 transient
48 unity
49 inductance
50. above 132kv
Subscribe to:
Posts (Atom)